Restroom Facilities / Bathing and Toilet Facilities - General Requirements

Bathing and Toilet Facilities - General Requirements

All sanitary facilities that serve buildings, facilities or portion of buildings that are required by handicapped regulations to be accessible to persons with disabilities shall comply. Separate facilities are required where provided for the non disabled. Where unisex facilities are provided for the non disabled, such unisex facilities shall be provided for persons with disabilities. Where facilities are to be used solely by small children, the specific heights may be adjusted to meet their accessibility needs.

Toilet Room Fixtures and Accessories: Basic Requirements

Fixture/Element Specification
Water closet height Min. 17" to max. 19"
Water closet flush control Max. 44" above floor
Grab bars 1 1/4" ø - 1 1/2" ø mounted at 33" above floor with 1 1/2" wall clearance
Towel, sanitary napkins and waste receptacles Max. 40" above floor
Urinal Min. 14" from wall and 17" above floor with operable control at max. 44" above the floor

Single-Accommodation Toilet Facility

The following specifications apply to single-accommodation (single-user) toilet facilities:

PLAN VIEW REQUIREMENTS:

- 18" min. centerline of fixture to wall
- 60" min. clear turning diameter
- 28" to edge of water closet
- 32" min. clear maneuvering space
- 18" min. to 32" min. clear space dimensions
- Flush activator on wide side
- 36" min. grab bar and 42" min. grab bar locations

Accessible Water Closet Compartment Within Multiple-Accommodation Facility

When accessible compartments are provided within multiple-accommodation toilet rooms:

PLAN VIEW REQUIREMENTS:

- 18" min. centerline to wall
- 32" min. to edge of water closet
- 60" min. clear turning space
- Flush activator on wide side

Side Elevation Requirements

VERTICAL CLEARANCES AND MOUNTING:

- 36" min grab bar
- 42" min grab bar
- All dispensers set back to prevent obstruction
- 17" - 19" A.F.F. (above finished floor) water closet height

These diagrams illustrate the specific requirements of these regulations and are intended only as an aid for building design and construction.

For detailed specifications on reach requirements that apply to controls and dispensers, see Forward Reach and Side Reach Requirements.